1. Power supply voltage: the rated value is AC 220V, and the fluctuation cannot exceed ±20%;
2. Ambient temperature: -25℃~55℃;
3. Relative humidity: the maximum relative humidity is 90% (at 20℃);
4. Altitude Height: no more than 2000m;
5. Environmental conditions: no explosive and flammable dangerous media, no gases that corrode metals and conductive dust that damage electrical insulation;
JKW-3FA Hybrid compensation intelligent reactive power compensation controller
Main purpose and scope of application
JKW-3F series intelligent reactive power compensation controller (hereinafter referred to as the controller), adopts advanced high-speed microprocessor control technology, real-time sampling of three-phase voltage and three-phase current signals, and the compensation capacitor of the capacitor cabinet is adopted The control scheme of single-phase independent compensation plus three-phase simultaneous compensation is very suitable for the automatic control of reactive power compensation capacitor cabinets in low-voltage power systems with unbalanced three-phase loads. This product complies with: industry standard JB/T9663-2013 (our company is the main drafting unit of this standard).
Model and meaning
Working conditions
1. Power supply voltage: the rated value is AC 220V, and the fluctuation cannot exceed ±20%;
2. Ambient temperature: -25℃~55℃;
3. Relative humidity: the maximum relative humidity is 90% (at 20℃);
4 , Altitude: no more than 2000m;
5. Environmental conditions: no explosive and flammable dangerous media, no gases that corrode metals and conductive dust that damage electrical insulation;
Main technical parameters
1. Rated current: AC 0~5A;
2. Rated voltage: AC 220V±20%;
3. Contact capacity: dynamic DC12V/50mA (static AC220V/7A) per branch;
4. Current input impedance: ≤0.02Ω;
5. Shell protection grade: IP30;
6. Frequency: 50Hz;
7. Sensitivity: 20mA;
8. Insulation voltage: 690V;
Features
1. Real-time display of three-phase network conditions: including system voltage, system current, active power, reactive power, power factor, various control parameters, etc.
2. Automatically identify the polarity of the sampling signal, and there is no concern about the polarity of the wiring.
3. With setting parameter memory function, data will not be lost after power failure.
4. It has protection functions such as over-voltage and under-voltage, phase loss, etc.
5. With dual input threshold: it is required that the power factor is lower than the input threshold setting value and the reactive power is higher than the minimum set of capacitors before it can be input, effectively preventing switching oscillation.
6. It has a super-strong automatic optimization and switching function.
7. There is a settable re-investment lock time to ensure that the capacitor has enough discharge time before being turned on.
8. Various parameters are all digitally adjustable, which can be widely applied to different power grid conditions.
9. Strong anti-interference ability, can directly resist interference pulses from peripheral common mode amplitude 2000V.
10. The compensation scheme can be set as full single-phase compensation, single-phase compensation plus three-phase compensation, and full three-phase compensation.
11. There are static and dynamic output modes.
Factory setting values of various parameters
Code | meaning | Setting value | Adjustable range |
P-00 | Current polarity recognition method | AUTO | AUTO automatic/HAND manual |
P-01 | Power factor input threshold | 0.95 | Perceptual 0.800~1.000 |
P-02 | Power factor cut off threshold | 1 | Perceptual 0.900~Capacitive -.900 |
P-03 | Input delay | 10s | 0.1~100s |
P-04 | Cut-off delay | 10s | 0.1~100s |
P-05 | Overvoltage threshold | 245V | 220V~300V |
P-06 | Capacitor discharge delay | 0 | 0~240s |
P-07 | Sampling current transformer ratio | 500 | 5~9000 |
P-08 | Compensation capacitor solution | 3F07(2F06) | 0F16-5F01(0F12~4F00) |
C-01~C-12 | Capacitance capacity of each branch controlled | 5 | 0~200kvar |
Main specifications and models
Product number | Hole Size | Sampling voltage | Signal frequency | Control output | monitor | Total Weight | Replace the old model |
JKW-3FC-12D | 113×113 | Three-phase four-wire | 50/60Hz | 12 DC | Luminous Digital | 0.9kg | JKWF12-DCS |
JKW-3FC-12J | 113×113 | Three-phase four-wire | 50/60Hz | 12-way contacts | Luminous Digital | 0.9kg | JKWF12-JCS |
JKW-3FA-16D | 139×139 | Three-phase four-wire | 50/60Hz | 16 channels DC | Luminous Digital | 0.95kg | JKWF18-DCS-16 |
JKW-3FA-16J | 139×139 | Three-phase four-wire | 50/60Hz | 16 contacts | Luminous Digital | 0.95kg | JKWF18-JCS-16 |
JKW-3FA-19D | 139×139 | Three-phase four-wire | 50/60Hz | 19 DC | Luminous Digital | 0.95kg | - |
Wiring schematic diagram
If you have any enquiry about quotation or cooperation,please free to email us ata65148373@163.comor use the following enquiry form,Our sales representative will contact you within 24 hous.thank you for your interest in our products.
Share our Product over the Social Networks
Search across our website