1. The contactor is equipped with a current-limiting resistor, which can suppress the closing inrush current within the allowable range;
2. The contactor is a direct-acting double-breakpoint structure, with flexible action mechanism, convenient manual inspection and compact structure;
3. Contactor terminal It is covered by an insulating cover, which is safe and reliable;
4. The contactor can be fastened with screws, or it can be buckled on a 35mm or 75mm standard mounting rail;
CJ19-25 32 43 Switching capacitor contactor
Main purpose and scope of application
CJ19 series switching capacitor contactor is suitable for AC 50Hz, rated working voltage to 380V/660V power system, for low-voltage reactive power compensation equipment to put or cut capacitors to improve power factor. The contactor is equipped with an inrush current suppression device, which can effectively reduce the impact of the closing inrush current on the capacitor, and can replace the original switching device consisting of three XD1 current-limiting reactors and a CJ10 contactor.
This product complies with: national standards GB14048.1, GB14048.4, GB14048.5, IEC60947-4-1.
Model and meaning
Contactor model | Auxiliary contact combination | Number of contacts | Contact mark | ||
Normally open (moving and closing) | Normally closed (moving off) | Normally open (moving and closing) | Normally closed (moving off) | ||
CJ19-25 CJ19-32 CJ19-43 | 20E | 2 | - | 13, 14, 23, 24 | - |
02E | - | 2 | - | 11, 12, 21, 22 | |
11E | 1 | 1 | 13, 14 | 21, 22 | |
CJ19-63 CJ19-95 | 21E | 2 | 1 | 13, 14, 33, 34 | 21, 22 |
12E | 1 | 2 | 13, 14 | 21, 22, 31, 32 | |
CJ19-115 CJ19-150 CJ19-170 | 10E | 1 | - | 13, 14 | - |
01E | - | 1 | - | 11, 12 |
Working principle
When the control circuit is energized, the contactor is closed, and the upper main contact connected in the current-limiting resistance line is connected before the lower main contact, so as to suppress the inrush current. After the completion, it will be disconnected and reset instantly, during which the lower main contact The head enters normal work, and when the circuit is disconnected, it is completed by the lower main contact. Each performs its duties. Because the current-limiting resistor is connected instantaneously, it will not cause long-term power waste and burnout of the resistor.
Working conditions
1. The altitude of the installation site should not exceed 2000m;
2. The upper limit of the ambient air temperature should not exceed +40℃, and the lower limit should not be lower than -5℃;
3. The relative humidity of the installation site should be +40 at the highest temperature The temperature does not exceed 50%, and the relative humidity can be higher at a lower temperature. The monthly average minimum temperature of the wettest month does not exceed +20℃, and the average maximum relative humidity of the month does not exceed 90%, due to temperature changes. Measures must be taken for the condensation on the product;
4. Installation conditions: The installation incline to the vertical surface does not exceed ±5 °;
5. Pollution degree: Level 3;
6. Shock and vibration: In the absence of significant shaking, shock and vibration The place;
Structural features
1. The contactor is equipped with a current-limiting resistor, which can suppress the closing inrush current within the allowable range;
2. The contactor is a direct-acting double-breakpoint structure, with flexible action mechanism, convenient manual inspection and compact structure;
3. Contactor The terminal is covered by an insulating cover, which is safe and reliable;
4. The contactor can be fastened with screws, or it can be buckled on a 35mm or 75mm standard mounting rail;
Main technical parameters
model | CJ19-25 | CJ19-32 | CJ19-43 | CJ19-63 | CJ19-95 | CJ19-115 | CJ19-150 | CJ19-170 | |||
Conventional heating current Ith A | 25 | 32 | 43 | 63 | 95 | 250 | 250 | 250 | |||
Rated working current Ie AC-6b A | 17 | 25 | 29 | 43 | 74 | 87 | 115 | 130 | |||
Controllable capacitor kvar |
230V-250V | 6 | 9 | 10 | 15 | 29 | 35 | 45 | 52 | ||
400V-450V | 12 | 15 | 20 | 30 | 50 | 60 | 80 | 90 | |||
690V | 10 | 15 | 20 | 30 | 45 | 55 | 65 | 75 | |||
Equipped with fuse model | RT16-25 | RT16-32 | RT16-50 | RT16-63 | RT16-125 | RT16-160 | RT16-160 | RT16-250 | |||
Inrush current suppression capability (current limit multiple) times | 20In | ||||||||||
Line Circle |
Working voltage V | 220, 380 or according to user requirements | |||||||||
Range of motion | 0.85~1.1Us | ||||||||||
Power consumption VA |
start | 90 | 230 | 300 | |||||||
Hold | 8 | 20 | twenty two | ||||||||
Electrical life 104 times | 10 | 8 | 6 | 2 | |||||||
Mechanical life 104 times | 100 | 80 | 60 | 20 | |||||||
Maximum operating frequency times/h | 300 | 120 | |||||||||
Rated insulation voltage V | 500 | 660 | 1000 | ||||||||
Auxiliary contact | Conventional heating current A | 10 | |||||||||
Electric life | AC-15 360VA | 12 | |||||||||
104 times | DC-13 33W | 12 | |||||||||
The smallest load that can be connected | 6V×10mA | ||||||||||
Current limiting resistor input time ms | 7~9 |
Shape and installation dimensions
CJ19 switching capacitor contactor | Amax | Bmax | Cmax |
CJ19-25 | 45 | 160 | 124 |
CJ19-32 | 57 | 157 | 132 |
CJ19-43 | 57 | 157 | 136 |
CJ19-63 | 76 | 175 | 150 |
CJ19-95 | 85 | 195 | 160 |
CJ19-115 | 121 | 220 | 156 |
CJ19-150 | 121 | 220 | 156 |
CJ19-170 | 121 | 220 | 156 |
Ordering instructions
1. When ordering, it must be pointed out:
a. The complete name and model of the contactor;
b. The rated control power supply voltage and frequency of the coil;
c. The order quantity;
d. The auxiliary contact composition code.
2. Order example: CJ19-43/11E, 220V/50Hz; it means that the current of the switching capacitor contactor is 43A, the coil voltage is 220V 50Hz, and the auxiliary contact has one normally open and one normally closed.
If you have any enquiry about quotation or cooperation,please free to email us ata65148373@163.comor use the following enquiry form,Our sales representative will contact you within 24 hous.thank you for your interest in our products.
Share our Product over the Social Networks
Search across our website