1. In the case of unbalanced three-phase leakage, electric shock and electric leakage can
operate reliably; 2. It can be put into operation normally under the condition of low insulation level of the line and large leakage current;
3. Strong anti-interference, lightning and power grid harmony Under interference conditions such as wave, line transient overvoltage, etc., no malfunction;
4. No action when line leakage is suddenly reduced, which reduces unnecessary power outages and has a higher commissioning rate;
JD6L Phase detection and amplitude leakage relay
Main purpose and scope of application:
JD6L series phase and amplitude detection leakage relays are combined with AC contactors or circuit breakers to form leakage protection devices. It is suitable for low-voltage (380/220V) power distribution system where the neutral point is directly grounded. The main function is to provide indirect contact protection for the leakage of lines and equipment. Due to the new technology of phase and amplitude detection, the insensitivity of electric shock is eliminated, and it has the characteristics of energy saving and noise reduction. It is especially suitable for the use of power grids with poor line conditions and unbalanced three-phase leakage to improve the safe operation of the power grid.
This product complies with: National Standard GB/Z6829, GB/T22387.
Working conditions
1. Ambient temperature: the upper limit does not exceed +40℃, and the average temperature within 24 hours does not exceed +35℃, and the lower limit does not fall below -25℃;
2. Relative humidity: +40℃ does not exceed 50%, +25℃ does not More than 90%;
3. Altitude: ≤2000m;
4. Pollution level: Level 3;
Model and meaning
Structural features
1. In the case of unbalanced three-phase leakage, electric shock and electric leakage can
operatereliably;2. It can be put into operation normally under the condition of low insulation level of the line and large leakage current;
3. Strong anti-interference, lightning, Under the interference of power grid harmonics and transient over-voltage of the line, no malfunction;
4. No action when the line leakage is suddenly reduced, which reduces unnecessary power outages and has a high commissioning rate;
5. Energy-saving silent operation is in contact with the mating The working voltage of the coil of the device is 380V and 220V, which can be used for long-term operation without burning the coil;
6. There is a test power transmission function when themachine isturned on. 20~30 seconds after tripping, automatic reclosing, safe and labor-saving;
Main technical parameters
1. Rated voltage: 380V/220V
2. Rated frequency: 50Hz
3. Rated current: 250A, 400A, 630A, 800A
4. Auxiliary power supply rated voltage: 220V
5. Rated leakage current: 300mA (adjustable 300mA/ 500mA)
6. Rated leakage current: 150mA, 250mA
7. Rated electric shock current: 50mA/75mA
8. Rated electric shock current: 25mA/38mA
9. Maximum breaking time: 0.2s
10. Delayed reclosing: 20 ~30s
11. Energy saving effect: active power saving rate>80%
Wiring schematic diagram
Shape and installation dimensions
Series model, type and matching contactor, circuit breaker
model | Leakage value | Type | Matching main switch model |
JD6L-250A | 300mA |
Standard energy-saving type (small ring φ46mm) |
Only CJ type 63A~250A AC contactors can be equipped, and 40A and below contactors can not be equipped, and energy-saving contactors or energy-saving coils cannot be equipped. |
JD6L-250A-K | 300/500mA (adjustable) | ||
JD6L-400A | 300mA |
Standard energy-saving type (Central φ60mm) |
Only CJ type 63A~400A AC contactors can be equipped, 40A and below contactors, energy-saving contactors or energy-saving coils cannot be equipped. |
JD6L-400A-K | 300/500mA (adjustable) | ||
JD6LB-250A | 300mA |
No energy-saving type (small ring φ46mm) |
Can be equipped with circuit breaker (undervoltage coil, excitation coil); |
JD6LB-250A-K | 300/500mA (adjustable) | ||
JD6LB-(400~630)A | 300mA |
No energy-saving type (Central φ60mm) |
|
JD6LB-(400~630)AK | 300/500mA (adjustable) | ||
JD6LB-(630~800)AK | 300/500mA (adjustable) | No energy-saving type (large ring φ86mm) | |
JD6LB-CJ-630A | 300mA | Passive output type (Central φ60) | Can be equipped with contactors of any type and specifications, or energy-saving contactors |
JD6LB-CJ-800A | 300mA | Passive output type (large ring φ86) |
The JD6L series has a variety of specifications. The user must carefully read the wiring diagram before installing the wiring to avoid unnecessary damage to the leakage relay, contactor or circuit breaker due to errors.
Ordering instructions
should be noted when ordering: standard type (energy-saving mode) or B type (contact output), main circuit rated current A, whether it is adjustable type (with K) or ordinary type (without K); Phase discriminating energy-saving leakage relay, main circuit 250A, leakage current adjustable, 10 pieces, model should be JD6L-250A-K, 10 pieces.