Delayed reclosing time: 70% of rated voltage,
undervoltage action value: 120% of rated voltage (can be closed)
, overvoltage action value: action when any phase of ABC three-phase is missing (can be closed);
phase failure protection: functional module The power supply is directly taken from the three-phase power supply of the autonomous loop, which completely avoids the problem of phase loss and residual current protection not working.
ZUM1L-100/3N Residual current operated circuit breaker
Main purpose and scope of application
ZUM1L series residual current operated circuit breaker (referred to as leakage circuit breaker) is a multifunctional integrated leakage circuit breaker integrating leakage relay and molded case circuit breaker. Suitable for low-voltage power grids with three-phase four-wire neutral point directly grounded (TT grounding system), used to provide indirect contact protection against personal electric shock hazards, and also for ground faults, overcurrents, short circuits, and overvoltages of lines or electrical equipment , Undervoltage, lack of phase, and neutral line break on the power supply side for protection.
This product complies with: National Standard GB14048.2.
Model and meaning
Main technical parameters
1. Rated voltage: | 400V three-phase four-wire |
2. Rated insulation voltage: | 800V |
3. Rated current: | 100A shell frame 40A, 63A, 80A, 100A optional |
250A shell frame 100A, 160A, 200A, 250A optional | |
400A shell frame 250A, 315A, 350A, 400A optional | |
800A shell frame 500A, 630A, 700A, 800A optional | |
4. Rated frequency: | 50Hz |
5. Rated residual operating current: | 50/75/100/150/200/300/500/800/1000mA, |
6. Rated residual non-operation current 0.5I△n: Abrupt leakage action value: ≤50mA | Only four gears are selected for a single product, please refer to the value on the nameplate. |
7. Rated breaking time: | <0.2s/<0.5s can be set to automatically overlap once 20s~60s |
8. Delayed reclosing time: | 70% rated voltage |
9. Undervoltage action value: | 120% rated voltage (can be closed) |
10. Overvoltage action value: | Action when any phase of ABC three-phase is missing (can be closed); |
11. Phase loss protection: |
The functional module power supply is directly taken from the three-phase power supply of the autonomous loop, which completely avoids the problem of phase loss and residual current protection not working. |
12. Rated ultimate short-circuit breaking capacity and rated residual short-circuit making (breaking) capacity: | See table 1 |
13. Protection characteristics of overcurrent release: | See table 2 |
14. Classification of action characteristics: | AC type |
15. Product use category: | Class A (delay/instant two-stage protection) |
16. Reference temperature: | 40℃ |
17. The product conforms to: | GB14048.2 National Standard |
Table 1 Rated short-circuit breaking capacity and rated residual making and breaking capacity
Frame rating rated current A | Rated ultimate short-circuit breaking capacity lcu (effective value kA) | Rated short-circuit breaking capacity lcu (effective value kA) | Rated residual making and breaking capacity l△m (effective value kA) |
100 | 35 | twenty two | 8.75 |
250 | 50 | 35 | 12.5 |
400 | 50 | 35 | 12.5 |
630 | 65 | 42 | 16.25 |
800 | 65 | 42 | 16.25 |
Table 2 Protection characteristics of overcurrent release
Ambient air temperature -5℃~+40℃ | Test current | Trip time | status |
1.05In | No tripping within 2h | Cold start | |
1.30In | Trip within 2h | Hot start | |
Any suitable time | 10Imax | <0.2s | Cold start |
Note: ln overcurrent setting value Imax: frame grade current
Shape and installation dimensions
specification | Dimensions (mm) | Installation size (mm) | Mounting hole diameter (mm) | |||||
A | B | E | F | G | C | D | ||
100A | 231 | 121 | 45 | 62 | 170 | 60 | 211 | 4 |
250A | 240 | 140 | 45 | 84 | 177 | 70 | 202 | 4 |
400A | 336 | 197 | 82 | 99 | 246 | 96 | 272 | 6 |
630A | 355 | 228 | 76 | 106 | 261 | 116 | 285 | 6 |
800A | 355 | 228 | 76 | 106 | 261 | 116 | 285 | 6 |
Technical Parameters
Ordering instructions When placing an
order, please specify the
product model, rated current, rated residual current operating value, function code, and order quantity.
If you need to order ZUM1L, the rated current is 250A, whether the current gear is adjustable, the residual current action value is 75/150/300/500mA, 100 units.
If you have any enquiry about quotation or cooperation,please free to email us ata65148373@163.comor use the following enquiry form,Our sales representative will contact you within 24 hous.thank you for your interest in our products.
Share our Product over the Social Networks
Search across our website